Input type SINK
Input terminals Ixx (xx represents the terminal's number)
Number of inputs 14*
Maximum voltage for log. 0 3 V DC
Minimum voltage for log. 1 7 V DC
Maximum voltage 24 V DC
Configurable terminals P01, P02
Internal 12 V DC power supply positive pole (only for DI, AI, and AO) 12 V
Galvanic isolation Yes (if an external power supply is used)