Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
en:automation:02-glossary:analog-inputs-hidden [2018/09/04 06:55]
mkudlacek
en:automation:02-glossary:analog-inputs-hidden [2021/06/09 08:48] (current)
avsetula
Line 1: Line 1:
 ====== Analog inputs ====== ====== Analog inputs ======
-Analog inputs (AI) are for reading ​DC voltage ​or DC current. ​The actual range is 0-10V or 0-20mA, which is an industrial standard.  +Analog inputs (AI) are for measuring analog values such as DC voltagecurrent ​and resistanceThese values ​are produced by sensors ​which indicate multiple states ​such as thermometerstensometers,​ distance ​meters, ​lux meters ​etc.
-The inputs are suitable for reading ​values ​from analog ​sensors such as temperature sensorspressure ​meters, ​tensometers ​etc.+
  
-<WRAP center round tip 60%> +----
-On Neuron and Axon, the analog inputs can also measure resistance, making the AIs suitable for measuring temperature from resistive thermometers such as Pt100, Pt500, Pt1000 and Ni1000. +
-</​WRAP>​+
  
-===== Analog ​inputs ​Neuron and Axon ===== +<​html><​span class="​kbBlueText">​More information about analog ​inputs ​can be found in specific categories:</​span><​/html>\\
-The functionality of AIs on Neuron and Axon is different on Group 1 and Group 2/3 or Neuron extensions. ​+
  
-On Group 1, the analog input is only capable ​of measuring DC voltage in a range of 0-10V and DC current in a range of 0-20mA.+<​tile>​ 
 +| en:​hw:​007-patron:​description-of-io:​04-description-of-ai     | Patron ​            | :​en:​hw:​unipi-kb-icon-patron.png ​    | 
 +| en:​hw:​01-axon:​description-of-io:​04-description-of-ai ​       | Axon               | :​en:​hw:​unipi-kb-icon-axon.png ​      | 
 +| en:​hw:​02-neuron:​description-of-io:​04-description-of-ai ​     | Neuron ​            | :​en:​hw:​unipi-kb-icon-neuron.png ​    | 
 +| en:​hw:​03-unipi11:​description-of-io:​04-description-of-ai ​    | 1.1 & 1.1 Lite     | :​en:​hw:​unipi-kb-icon-1.png ​         | 
 +| en:​hw:​04-extensions:​description-of-io:​04-description-of-ai ​ | Extension modules ​ | :​en:​hw:​unipi-kb-icon-extension.png  |  
 +</​tile>​
  
-On Group 2 and 3 and on the Neuron extensions, the analog input is capable of:+ 
 +/* 
 +===== Analog inputs on Neuron and Axon ===== 
 +The functionality of AIs on Neuron and Axon is different on Group 1 and Group 2/3 and Neuron extensions.  
 + 
 +On Group 1, the analog input is capable of: 
 +  * measuring 0-10V DC 
 +  * measuring 0-20mA DC 
 + 
 +<WRAP center round tip 60%> 
 +The Group 1 is also capable of measuring the resistance, but this is achievable with [[en:​automation:​02-glossary:​analog-outputs-hidden|Analog output]]. 
 +</​WRAP>​ 
 + 
 +On Group 2 and 3 and the Neuron extensions, the analog input is capable of:
   * measuring 0-10V DC   * measuring 0-10V DC
   * measuring 0-2.5V DC with higher precision   * measuring 0-2.5V DC with higher precision
   * measuring of 0-20mA DC   * measuring of 0-20mA DC
-  * measuring of resistance 0-100kOhm via 2-wire method +  * measuring of resistance 0-100kOhm via 2-wire method 
-  * measuring of resistance 0-2kOhm via more precise 3-wire method+  * measuring of resistance 0-2kOhm via more precise 3-wire method 
 + 
 +Changing between modes depends on the [[en:​sw:​00-start|software]] you are using, please follow the relevant tutorial.  
 + 
 +==== Measuring voltage ==== 
 +==== Measuring current ====
  
 ===== Analog inputs on Unipi 1.1 ===== ===== Analog inputs on Unipi 1.1 =====
-The UniPi 1.1 has two analog inputs and they are only capable of measuring voltage in a range of 0-10V DC.+The Unipi 1.1 has two analog inputs and they are only capable of measuring voltage in a range of 0-10V DC. 
 + 
 +==== Measuring resistance ==== 
 +To measure resistance from the Unipi 1.1's AI (ie. by using PT1000 thermal probes), it is necessary to add a resistor according to the following scheme. 
 + 
 +{{:​en:​automation:​02-glossary:​unipi_ai.png?​300|}} 
 + 
 +   ​R_sens = the sensor itself 
 +   R_ref = the reference resistor 
 + 
 +There is also a input resistor inside of the AI with the value: 
 + 
 +   R_ai = 12200ohm 
 + 
 +<WRAP center round alert 60%> 
 +For R_sens >= 200ohm, use R_ref = 1k. For R_sens < 200ohm, use R_ref = 10k 
 +</​WRAP>​ 
 + 
 +The value at the AI is calculated from the voltage you read from the AI (V_ai)
  
 +             Vcc - V_ai     R_ref * R_ai
 +   ​R_sens = ------------ * --------------
 +                V_ai        R_ref + R_ai
 +                ​
 +The Vcc is the applied voltage (12V in the picture above).
 +*/