| - | ====== Powering Unipi PLCs through PoE ====== | + | ====== Powering Unipi units through PoE ====== |
| - | This tutorial describes the connection of Unipi controllers using 802.3at PoE+ splitter. This connection is useful especially if you need to place the PLC in locations lacking a conventional ~230V socket (ie. sensor stations). This tutorial will show you how to power the Unipi over Ethernet cable while retaining local network connectivity. | + | <WRAP group> |
| + | <WRAP half column 81%> | ||
| + | This tutorial describes the connection of Unipi controllers using 802.3at PoE+ splitter. The splitter must be supplemented and powered by a PoE injector or any PoE switch. This connection is useful especially if you need to place the controller | ||
| + | </ | ||
| + | <WRAP half column 15%> | ||
| + | ;;# | ||
| + | < | ||
| + | < | ||
| + | < | ||
| + | < | ||
| + | ;;# | ||
| + | </ | ||
| + | </ | ||
| == Components used in the tutorial == | == Components used in the tutorial == | ||
| * Cat6 network cable (RJ45) | * Cat6 network cable (RJ45) | ||
| * conductor (Cu, 0.5mm2) | * conductor (Cu, 0.5mm2) | ||
| - | * Planet IPOE-162S PoE splitter | + | * Planet IPOE-162S PoE splitter |
| - | * Planet | + | * Planet |
| - | * The switch used is just one of possible variants. You can use any 802.3at | + | * Unipi controller |
| - | * Unipi PLC | + | |
| ==== Connection example ==== | ==== Connection example ==== | ||
| - | {{ : | + | {{ : |
| == Planet IPOE-162S == | == Planet IPOE-162S == | ||
| - | - set the splitter for 24V voltage using the onboard switch | + | - set the splitter for 24 V⎓ voltage using the onboard switch |
| - connect the splitter’s V+ clamp to the PLC’s 24V clamp | - connect the splitter’s V+ clamp to the PLC’s 24V clamp | ||
| - connect the splitter’s V- clamp to the PLC’s GND clamp | - connect the splitter’s V- clamp to the PLC’s GND clamp | ||
| - | - using the network cable, connect the splitter’s Data Out port with the PLC’s ETH port | + | - using the network cable, connect the splitter’s |
| - | - plug an 802.3at PoE+ compatible network cable into the splitter‘s PoE In port | + | - plug an 802.3at PoE+ compatible network cable into the splitter‘s |
| == Planet GSD-908HP == | == Planet GSD-908HP == | ||
| - | - use one of the switch ports to connect | + | - connect |
| - | - repeat the step for any other additional splitter | + | - connect the WAN network cable into the **Ethernet** |
| - | - connect the WAN network cable into the port 9 | + | |
| ==== Technical data ==== | ==== Technical data ==== | ||
| - | Using a single splitter to power multiple | + | Using a single splitter to power multiple |
| \\ | \\ | ||
| \\ | \\ | ||
| Line 40: | Line 50: | ||
| \\ | \\ | ||
| < | < | ||
| - | - maximum load of the Neuron L403 = 24W | + | - maximum load of the Neuron L403 = 24 W |
| - | - maximum load of the splitter = 25W | + | - maximum load of the splitter = 25 W |
| - | * 25W – 24W = 1W | + | * 25 W – 24 W = 1 W |
| * the resulting value is a positive number = suitable | * the resulting value is a positive number = suitable | ||
| - | - maximum load of the switch = 100W | + | - maximum load of the switch = 100 W |
| - | * 100W ⁄ 24W = < | + | * 100 W ⁄ 24 W = < |
| __Based on these calculations, | __Based on these calculations, | ||
| Line 51: | Line 61: | ||
| \\ | \\ | ||
| < | < | ||
| - | - maximum load of the Patron S107 = 12W | + | - maximum load of the Patron S107 = 12 W |
| - | - maximum load of the splitter = 25W | + | - maximum load of the splitter = 25 W |
| - | * 25W – 12W = 13W | + | * 25 W – 12 W = 13 W |
| * the resulting value is a positive number = suitable | * the resulting value is a positive number = suitable | ||
| - | - maximum load of the switch = 100W | + | - maximum load of the switch = 100 W |
| - | * 100W ⁄ 12W = < | + | * 100 W ⁄ 12 W = < |
| __Based on these calculations, | __Based on these calculations, | ||
| Line 63: | Line 73: | ||
| < | < | ||
| - maximum power input: | - maximum power input: | ||
| - | * Patron L207 -> 17W (1x) | + | * Patron L207 -> 17 W (1×) |
| - | * Patron M207 -> 14.5W (2x) | + | * Patron M207 -> 14.5 W (2×) |
| - | * Patron S107 -> 12W (remaining) | + | * Patron S107 -> 12 W (remaining) |
| - | - maximum load of the splitter = 25W | + | - maximum load of the splitter = 25 W |
| - | * 25W – 12W = 13W | + | * 25 W – 12 W = 13 W |
| - | * 25W – 14.5W = 10.5W | + | * 25 W – 14.5 W = 10.5 W |
| - | * 25W – 17W = 8W | + | * 25 W – 17 W = 8 W |
| * the resulting value is a positive number = suitable | * the resulting value is a positive number = suitable | ||
| - | - maximum load of the switch = 100W | + | - maximum load of the switch = 100 W |
| - | * 100W – 17W – 2x14.5W = 54W | + | * 100 W – 17 W – 2 × 14.5 W = 54 W |
| - | * The remaining: | + | * The remaining: |
| __Based on these calculations, | __Based on these calculations, | ||