-====== ​Connection of Unipi using PoE splitter ​====== +====== ​Powering ​Unipi units through ​PoE ====== 
-This tutorial describes the connection of Unipi controllers using 802.3at PoE+ splitter. This connection is useful especially if you need to place the PLC in locations lacking a conventional ~230V socket (ie. sensor stations). This tutorial will show you how to power the Unipi over Ethernet cable while retaining ​the local network connectivity. ​+<WRAP group> 
 +<WRAP half column 81%> 
 +This tutorial describes the connection of Unipi controllers using 802.3at PoE+ splitter. The splitter must be supplemented and powered by a PoE injector or any PoE switch. This connection is useful especially if you need to place the controller ​in locations lacking a conventional ​110 / 230 V~ socket (ie. sensor stations). This tutorial will show you how to power the Unipi over Ethernet cable while retaining local network connectivity. 
 +</​WRAP>​ 
 +<WRAP half column 15%> 
 +;;# 
 +<​html><​span class="​dev-tag dev-patron">​Patron</​span></​html>​ \\ 
 +<​html><​span class="​dev-tag dev-neuron">​Neuron</​span></​html>​ \\ 
 +<​html><​span class="​dev-tag dev-gate">​Gate</​span></​html>​ \\ 
 +<​html><​span class="​dev-tag dev-axon">​Axon</​span></​html>​ 
 +;;# 
 +</​WRAP>​ 
 +</​WRAP>​
  
 == Components used in the tutorial == == Components used in the tutorial ==
   * Cat6 network cable (RJ45)   * Cat6 network cable (RJ45)
   * conductor (Cu, 0.5mm2)   * conductor (Cu, 0.5mm2)
-  * Planet IPOE-162S PoE splitter +  * Planet IPOE-162S PoE splitter ​([[https://​www.unipi.technology/​ipoe-162s-splitter-p432?​categoryId=15|e-shop link]]) 
-  * Planet ​GSD-908HP network switch +  * Planet ​IPOE-162 PoE injector ([[https://​www.unipi.technology/​ipoe-162-injector-p433?​categoryId=15|e-shop link]]) 
-    * Popsaný switch je pouze jedna z variant, lze použít libovolný switch s normou 802.3at ​PoE+ +  * Unipi controller ​
-  * Unipi Axon PLC +
  
 ==== Connection example ==== ==== Connection example ====
-{{ :​en:​automation:​unipi_-_switch_a_splitter.png |}}+{{ :​en:​automation:​unipi_-_injector_a_splitter.png?​direct ​|}} 
 == Planet IPOE-162S == == Planet IPOE-162S ==
-  - set the splitter for 24V voltage using the onboard switch+  - set the splitter for 24 V⎓ voltage using the onboard switch
   - connect the splitter’s V+ clamp to the PLC’s 24V clamp   - connect the splitter’s V+ clamp to the PLC’s 24V clamp
   - connect the splitter’s V- clamp to the PLC’s GND clamp   - connect the splitter’s V- clamp to the PLC’s GND clamp
-  - using the network cable, connect the splitter’s Data Out port with the PLC’s ETH port +  - using the network cable, connect the splitter’s ​**Data Out** port with the controller’s **ETH** port 
-  - plug an 802.3at PoE+ compatible network cable into the splitter‘s PoE In port+  - plug an 802.3at PoE+ compatible network cable into the splitter‘s ​**PoE In** port
  
 == Planet GSD-908HP == == Planet GSD-908HP ==
-  - use one of the switch ports to connect ​it with the PoE In port on the splitter via a suitable network cable +  - connect ​**Ethernet+DC** port to the **PoE In** port on the splitter via a suitable network cable 
-  - repeat the step for any other additional splitter +  - connect the WAN network cable into the **Ethernet** ​port
-  - connect the WAN network cable into the port +
- +
 ==== Technical data ==== ==== Technical data ====
-Using a single splitter to power multiple ​PLCs is not recommended! ​+Using a single splitter to power multiple ​controllers ​is not recommended! ​
 \\ \\
 \\ \\
-{{ :​en:​automation:​switch_splitter-table1_en.png?​direct |}}+{{ :​en:​automation:​switch_splitter-table1_en.png?​direct&​nolink ​|}}
 \\ \\
-{{ :​en:​automation:​switch_splitter-table2_en.png?​direct |}}+{{ :​en:​automation:​switch_splitter-table2_en.png?​direct&​nolink ​|}}
 \\ \\
-{{ :​en:​automation:​switch_splitter-table3_en.png?​direct |}}+{{ :​en:​automation:​switch_splitter-table3_en.png?​direct&​nolink ​|}}
 \\ \\
  
 ==== Calculating the maximum load – examples ==== ==== Calculating the maximum load – examples ====
 The calculations below are applicable for GSD-908HP PoE+ switch and IPOE-162S PoE+ splitter. The calculations below are applicable for GSD-908HP PoE+ switch and IPOE-162S PoE+ splitter.
 +
 \\ \\
-=1) Maximum number of connected Unipi Neuron L403 controllers ​== +<​html><​span class="​kbBlueText">​1) Maximum number of connected Unipi Neuron L403 controllers</​span></​html>​ 
-  - maximum load of the Neuron L403 = 25W +  - maximum load of the Neuron L403 = 24 W 
-  - maximum load of the splitter = 25W +  - maximum load of the splitter = 25 W 
-    * 25W – 24W 1W+    * 25 W – 24 W 1 W
     * the resulting value is a positive number = suitable     * the resulting value is a positive number = suitable
-  - maximum load of the switch = 100W +  - maximum load of the switch = 100 W 
-    * 100W ⁄ 24W = 4,166+    * 100 W ⁄ 24 W <​html><​span class="​avOrangeText">​4,166</​span></​html>​
  
 __Based on these calculations,​ we can **safely use 4 PoE+ powered Neuron L403'​s**__ __Based on these calculations,​ we can **safely use 4 PoE+ powered Neuron L403'​s**__
  
-=2) Maximum number of connected Unipi Axon S105 == +\\ 
-  - maximum load of the Axon S105 25W +<​html><​span class="​kbBlueText">​2) Maximum number of connected Unipi Patron S107</​span></​html>​ 
-  - maximum load of the splitter = 25W +  - maximum load of the Patron S107 12 W 
-    * 25W – 12W 13W+  - maximum load of the splitter = 25 W 
 +    * 25 W – 12 W 13 W
     * the resulting value is a positive number = suitable     * the resulting value is a positive number = suitable
-  - maximum load of the switch = 100W +  - maximum load of the switch = 100 W 
-    * 100W ⁄ 12W = 8,333+    * 100 W ⁄ 12 W <​html><​span class="​avOrangeText">​8,333</​span></​html>​
  
-__Based on these calculations,​ we can **safely use 8 PoE+ powered ​Axon S105's**__+__Based on these calculations,​ we can **safely use 8 PoE+ powered ​Patron S107's**__
  
-=3) Various combinations of Unipi models ​==+\\ 
 +<​html><​span class="​kbBlueText">​3) Various combinations of Unipi models</​span></​html>​
   - maximum power input:   - maximum power input:
-    * Axon L205 -> 19,5W (1x+    * Patron L207 -> 17 W (
-    * Axon M205 -> 16W (2x+    * Patron M207 -> 14.5 W (
-    * Axon S105 -> 12W (remaining) +    * Patron S107 -> 12 W (remaining) 
-  - maximum load of the splitter = 25W +  - maximum load of the splitter = 25 W 
-    * 25W – 12W 13W +    * 25 W – 12 W 13 W 
-    * 25W – 16W 9W +    * 25 W – 14.5 W 10.5 W 
-    * 25W – 19.5W 5.5W+    * 25 W – 17 W 8 W
     * the resulting value is a positive number = suitable     * the resulting value is a positive number = suitable
-  - maximum load of the switch = 100W +  - maximum load of the switch = 100 W 
-    * 100W – 19,5W – 2x16W 48.5W +    * 100 W – 17 W – 2 × 14.5 W 54 W 
-    * The remaining: ​48.5W ⁄ 12W = 4.041 +    * The remaining: ​54 W ⁄ 12 W = <​html><​span class="​avOrangeText">​4.5</​span></​html>​ 
-__Based on these calculations,​ a single switch **can power 1× Axon L205, 2× Axon M205 and 4× Axon S105**__ +__Based on these calculations,​ a single switch **can power 1× Patron L207, 2× Patron M207 and 4× Patron S107**__