| - | The following tutorial describes how to connect Unipi units with the Meanwell | + | The following tutorial describes how to connect Unipi units with the Mean Well DRC-60A power supply, which allows the output power to be backed up using a 12 V battery. It is also necessary to stabilize the power supply' |
| - | This power supply is used to supply power, but also to charge and maintain the charged battery | + | This power supply is used to supply power, but also to charge and maintain the charged battery. It can be operated, subject to the conditions described below, with all Unipi units and other selected Unipi equipment. In the event of a mains power failure, the power supply switches seamlessly to battery power mode. This achieves an uninterruptible power supply. |
| </ | </ | ||
| <WRAP half column 15%> | <WRAP half column 15%> | ||
| ;;# | ;;# | ||
| + | < | ||
| < | < | ||
| < | < | ||
| Line 27: | Line 28: | ||
| === Elements used === | === Elements used === | ||
| * Wires of different colours (Cu, 0.5mm2) | * Wires of different colours (Cu, 0.5mm2) | ||
| - | * Switched power supply | + | * Switched power supply |
| - | * DC/DC converter | + | * DC/DC converter |
| - | * Any 12 V⎓ acid-lead battery | + | * Any 12 V⎓ acid-lead battery (e.g. CSB GP12170 12V/17Ah) |
| * Unipi Patron S207 unit | * Unipi Patron S207 unit | ||
| ===== Description of the devices used ===== | ===== Description of the devices used ===== | ||
| - | The **DRC-60A** power supply can be supplied with an input voltage of 110 / 230 V~. The power supply' | + | The **DRC-60A** power supply can be supplied with an input voltage of 110 / 230 V~. The power supply' |
| - | The power supply powers the connected load (Unipi unit) and simultaneously charges and maintains the battery | + | The power supply powers the connected load (Unipi unit) and simultaneously charges and maintains the battery. The total output current of the power supply is up to 4.3 A, of which 1.5 A is reserved for charging the battery and 2.8 A for the load at the output. |
| ---- | ---- | ||
| Line 48: | Line 49: | ||
| ==== Wiring diagram ==== | ==== Wiring diagram ==== | ||
| - | {{ : | + | {{ : |
| ;#; | ;#; | ||
| //Fig.1 - Wiring diagram of DRC-60A, DDR-15G-24, CSB GP12170 and Unipi Patron S207// | //Fig.1 - Wiring diagram of DRC-60A, DDR-15G-24, CSB GP12170 and Unipi Patron S207// | ||
| Line 59: | Line 60: | ||
| * The conductor from the converter terminal **+Vo [1]** is connected to the first terminal of the **Bat.Low** signal relay and the first terminal of the **AC OK** relay. | * The conductor from the converter terminal **+Vo [1]** is connected to the first terminal of the **Bat.Low** signal relay and the first terminal of the **AC OK** relay. | ||
| * The second contact of the **Bat.Low** signal relay is connected to digital input **DI1** and the second contact of the **AC OK** relay is connected to **DI2**. | * The second contact of the **Bat.Low** signal relay is connected to digital input **DI1** and the second contact of the **AC OK** relay is connected to **DI2**. | ||
| - | * Before connecting the battery | + | * Before connecting the battery, the maximum output voltage of the power supply must first be set using the **+V ADJ** trimmer. The voltage must match the holding voltage of the battery, in the case of our wiring the voltage is set to 13.7 V⎓. |
| - | * The negative terminal of the battery is connected to the **-Bat.** power supply terminal. The positive terminal is connected to the **+Bat.**. | + | * The negative terminal of the battery is connected to the **-Bat.** power supply terminal |
| * Finally, connect the conductors (**⏚**, **N**, **L**) to the respective terminals of the power supply. | * Finally, connect the conductors (**⏚**, **N**, **L**) to the respective terminals of the power supply. | ||
| ===== Useful tips ===== | ===== Useful tips ===== | ||
| - | * Before the input voltage is connected for the first time, the power supply output is disconnected even when the battery is /*FIXME - opraveno na jednotné číslo*/ | + | * Before the input voltage is connected for the first time, the power supply output is disconnected even when the battery is connected and fully charged. Therefore, the input voltage must also be connected for full operation. When the input voltage is subsequently disconnected, |
| * When selecting the power supply protection, a current surge (inrush current) of up to 60 A must be taken into account when switching the input of the power supply. | * When selecting the power supply protection, a current surge (inrush current) of up to 60 A must be taken into account when switching the input of the power supply. | ||