Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
| en:automation:ups-meanwell-hidden [2021/08/03 08:24] – [Wiring description] lpolcerova | en:automation:ups-meanwell-hidden [2025/09/23 14:32] (current) – added edge ofojt | ||
|---|---|---|---|
| Line 1: | Line 1: | ||
| - | ====== Backup power supply for Unipi units ====== | + | < |
| + | <a href="/ | ||
| + | <a href="# | ||
| + | </ | ||
| + | |||
| + | ====== Backup power supply for Unipi units (DRC-60B) | ||
| <WRAP group> | <WRAP group> | ||
| <WRAP half column 81%> | <WRAP half column 81%> | ||
| - | The following tutorial describes how to connect Unipi units with the Meanwell | + | The following tutorial describes how to connect Unipi units with the Mean Well DRC-60B power supply, which allows the output power to be backed up using batteries. It is also necessary |
| This power supply is used to supply power, but also to charge and maintain charged batteries. It can be operated, subject to the conditions described below, with all Unipi units and other selected Unipi equipment. In the event of a mains power failure, the power supply switches seamlessly to battery power mode. This achieves an uninterruptible power supply. | This power supply is used to supply power, but also to charge and maintain charged batteries. It can be operated, subject to the conditions described below, with all Unipi units and other selected Unipi equipment. In the event of a mains power failure, the power supply switches seamlessly to battery power mode. This achieves an uninterruptible power supply. | ||
| Line 9: | Line 14: | ||
| <WRAP half column 15%> | <WRAP half column 15%> | ||
| ;;# | ;;# | ||
| + | < | ||
| < | < | ||
| < | < | ||
| Line 22: | Line 28: | ||
| === Elements used === | === Elements used === | ||
| * Wires of different colours (Cu, 0.5mm2) | * Wires of different colours (Cu, 0.5mm2) | ||
| - | * Switching | + | * Switched |
| - | * DC/DC converter | + | * DC/DC converter |
| - | * Any 12V acid-lead batteries (e.g. 2x CSB HR1234W 12V/9Ah) | + | * Any 12 V⎓ acid-lead batteries (e.g. 2× CSB HR1234W 12V/9Ah) |
| * Unipi Patron S207 unit | * Unipi Patron S207 unit | ||
| - | ===== Device description | + | ===== Description of the devices used ===== |
| - | The DRC-60B power supply can be supplied with an input voltage of 110 – 240 V~. The power supply' | + | The **DRC-60B** power supply can be supplied with an input voltage of 110 / 230 V~. The power supply' |
| The power supply powers the connected load (Unipi unit) and simultaneously charges and maintains the batteries. The total output current of the power supply is up to 2.15 A, of which 0.75 A is reserved for charging the batteries and 1.4 A for the load at the output. | The power supply powers the connected load (Unipi unit) and simultaneously charges and maintains the batteries. The total output current of the power supply is up to 2.15 A, of which 0.75 A is reserved for charging the batteries and 1.4 A for the load at the output. | ||
| Line 49: | Line 55: | ||
| ==== Wiring description ==== | ==== Wiring description ==== | ||
| - | * First, connect the output voltage (**+V**, **-V**) of the DRC-60B power supply to the input terminals of the DDR-15G-24 | + | * First, connect the output voltage (**+V**, **-V**) of the DRC-60B power supply to the input terminals of the DDR-15G-24 |
| - | * The output voltage from the inverter | + | * The output voltage from the converter |
| - | * The conductor from the inverter | + | * The conductor from the converter |
| - | * The conductor from the inverter | + | * The conductor from the converter |
| - | * The second contact of the **Bat.Low** signal relay is connected to digital input **DI1** and the second contact of the **AC OK** relay is connected to **DI2** | + | * The second contact of the **Bat.Low** signal relay is connected to digital input **DI1** and the second contact of the **AC OK** relay is connected to **DI2**. |
| - | * The batteries must be connected in series: the positive terminal of battery 1 is connected to the negative terminal of battery 2 | + | * Before connecting the batteries, the maximum output voltage of the power supply must first be set using the **+V ADJ** trimmer. The voltage must match the holding voltage of the batteries, in the case of our wiring the voltage is set to 27.4 V⎓ to achieve a voltage of 13.7 V⎓ on each of the batteries. |
| - | * The negative terminal of battery 1 is then connected to the **-Bat.** power supply terminal. The positive terminal of battery 2 is connected to the **+Bat.** | + | * The batteries must be connected in series: the positive terminal of battery 1 is connected to the negative terminal of battery 2. |
| - | * Finally, connect the conductors (**⏚**, **N**, **L**) to the respective terminals of the power supply | + | * The negative terminal of battery 1 is then connected to the **-Bat.** power supply terminal. The positive terminal of battery 2 is connected to the **+Bat.**. |
| + | * Finally, connect the conductors (**⏚**, **N**, **L**) to the respective terminals of the power supply. | ||
| ===== Useful tips ===== | ===== Useful tips ===== | ||
| - | * Before the input voltage is connected for the first time, the power supply output is disconnected even when the batteries are connected and fully charged. Therefore, the input voltage must also be connected for full operation. When the input voltage is subsequently disconnected, | + | * Before the input voltage is connected for the first time, the power supply output is disconnected even when the batteries are connected and fully charged. Therefore, the input voltage must also be connected for full operation. When the input voltage is subsequently disconnected, |
| * When selecting the power supply protection, a current surge (inrush current) of up to 60 A must be taken into account when switching the input of the power supply. | * When selecting the power supply protection, a current surge (inrush current) of up to 60 A must be taken into account when switching the input of the power supply. | ||
| - | * Neither the power supply nor the inverter | + | * Neither the power supply nor the converter |
| * The input of the power supply should be preferably treated with a suitable surge arrester. | * The input of the power supply should be preferably treated with a suitable surge arrester. | ||
| * The DRC-60B power supply meets the requirements for safety transformers and is a small safe voltage (SELV) power supply. | * The DRC-60B power supply meets the requirements for safety transformers and is a small safe voltage (SELV) power supply. | ||
| Line 73: | Line 80: | ||
| ==== Documentation ==== | ==== Documentation ==== | ||
| - | * {{ : | + | * {{ : |
| - | * {{ : | + | * {{ : |
| * [[cs: | * [[cs: | ||