| + | **M537 Section 2** analog inputs, can perform accurate measurement of current, voltage or resistance. Measurement mode needs to be set first in the control software. In voltage and resistance mode you can choose from two accuracy modes. The measured value is of **real** type and corresponds with the measured input value (V⎓, mA, Ω). | ||
| + | |||
| + | This type of analog input (M537 Section 2) supports the following modes: | ||
| + | * 0–10 V⎓ voltage | ||
| + | * 0–2 V⎓ voltage | ||
| + | * 4–20 mA current | ||
| + | * 2 kΩ resistance, 75–2000 Ω (two-wire) | ||
| + | * 20 kΩ resistance, 1–20 kΩ (two-wire) | ||