Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
Last revision Both sides next revision
en:hw:03-unipi11:description-of-io:03-description-of-ro [2020/12/16 12:54]
jan_kozak
en:hw:03-unipi11:description-of-io:03-description-of-ro [2022/07/12 13:23]
avsetula [Relay outputs]
Line 2: Line 2:
  
 /* Úvodní popis RO na Unipi 1.1 / Lite */ /* Úvodní popis RO na Unipi 1.1 / Lite */
 +<WRAP group>
 +<WRAP half column 81%>
 Relay outputs are terminated on terminals labelled by a switch schematic sign and serve for switching two-state devices with alternating or current voltage. The **COM** terminal is common, serving as input for switching voltage. **NO** and **NC** terminals are used as the switching voltage output.  ​ Relay outputs are terminated on terminals labelled by a switch schematic sign and serve for switching two-state devices with alternating or current voltage. The **COM** terminal is common, serving as input for switching voltage. **NO** and **NC** terminals are used as the switching voltage output.  ​
-  * NO - in the default state (no voltage), contacts are disengaged +  ​* **NO** - in the default state (no voltage), contacts are **disengaged** 
-  * NC - in the default state (no voltage), contacts are engaged+  ​* **NC** - in the default state (no voltage), contacts are **engaged** 
 +</​WRAP>​ 
 +<WRAP half column 15%> 
 +;;# 
 +<​html><​span class="​dev-tag dev-unipi11">​Unipi&​nbsp1.1</​span></​html>​ 
 +;;# 
 +</​WRAP>​ 
 +</​WRAP>​
  
-Switching ​of each relay is indicated by LED with the corresponding ​labelling. Overload and short circuit ​protection ​are provided by an external ​circuit breakerideally one for each output ​or group. Nominal current and the circuit breaker'​s ​type is to be selected according to the load and its characteristic considering ​the maximum current on the output ​or output group+The state (On/​Off) ​of each relay is indicated by LED with corresponding ​label. Overload and overvoltage ​protection ​should be provided ​externally ​by circuit breaker ​(ideally one for each output). Nominal current and circuit breaker type should ​be selected according to the load and its characteristics concerning ​the maximum current on the output. ​
  
-<WRAP center round info 95%> +<WRAP center round important ​95%> 
-**Note:** \\ +**Warning:** \\ 
-If an induction ​load is connected (eg. electric ​motor, relay coilcontactor ​or power cables in large installations), ​we recommend protecting ​relay outputs with a suitable ​external element (such as varistor, RC circuit or a suitable diode). ​+If an inductive ​load is connected (e.g., electric ​motors, relay coils, contactors, or even the cables in extensive electric ​installations), ​it is necessary to protect the relay outputs with a corresponding ​external element (e.g., varistor, RC circuit or a suitable diode). ​
  
-If a capacitive load is connected (eg. power supply for LED lighting), we recommend protecting ​relay contacts against inrush current by connecting a suitable ​thermistor to the relay'​s output+If a capacitive load is connected (e.g., power sources of LED lights), it is necessary to protect the relay contacts against inrush current by connecting a corresponding ​thermistor to the relay'​s output
 </​WRAP>​ </​WRAP>​