 Relay outputs are terminated on terminals labelled by a switch schematic sign and serve for switching two-state devices with alternating or current voltage. The **COM** terminal is common, serving as input for switching voltage. **NO** and **NC** terminals are used as the switching voltage output.  ​ Relay outputs are terminated on terminals labelled by a switch schematic sign and serve for switching two-state devices with alternating or current voltage. The **COM** terminal is common, serving as input for switching voltage. **NO** and **NC** terminals are used as the switching voltage output.  ​
-  * NO - in the default state (no voltage), contacts are disengaged +  ​* **NO** - in the default state (no voltage), contacts are **open** 
-  * NC - in the default state (no voltage), contacts are engaged+  ​* **NC** - in the default state (no voltage), contacts are **closed**
 </​WRAP>​ </​WRAP>​
 <WRAP half column 15%> <WRAP half column 15%>
Line 17: Line 17:
 The state (On/Off) of each relay is indicated by a LED with a corresponding label. Overload and overvoltage protection should be provided externally by a circuit breaker (ideally one for each output). Nominal current and circuit breaker type should be selected according to the load and its characteristics concerning the maximum current on the output. ​ The state (On/Off) of each relay is indicated by a LED with a corresponding label. Overload and overvoltage protection should be provided externally by a circuit breaker (ideally one for each output). Nominal current and circuit breaker type should be selected according to the load and its characteristics concerning the maximum current on the output. ​
  
-<WRAP center round info 95%>+<WRAP center round important ​95%> 
 +**Warning:​** \\ 
 +If an inductive load is connected (e.g., electric motors, relay coils, contactors, or even the cables in extensive electric installations),​ it is necessary to protect the relay outputs with a corresponding external element (e.g., varistor, RC circuit or a suitable diode). ​
  
-**Note:** \\ +If a capacitive ​load is connected (e.g., power sources of LED lights), ​it is necessary to protect the relay contacts against inrush current by connecting a corresponding thermistor to the relay'​s output. ​
-If an inductive ​load is connected (egelectric motors, relay coils, contactors or even the cables in extensive electric installations),​ we recommend protecting the relay outputs by a corresponding external element (egvaristorRC circuit or a suitable diode).  +
- +
-If a capacitive load is connected (eg. power sources of LED lights), ​we recommend protecting ​relay contacts against inrush current by connecting a corresponding thermistor to the relay'​s output. ​+
 </​WRAP>​ </​WRAP>​