 ====== Analog inputs ====== ====== Analog inputs ======
 +<WRAP group 100%>
 +<WRAP half column 81%>
 +In this tutorial, we are going to demonstrated how to use different modes of analog inputs.
 +</​WRAP>​
 +<WRAP half column 15%>
 +;;#
 +<​html><​span class="​dev-tag dev-patron">​Patron</​span></​html>​ \\
 +<​html><​span class="​dev-tag dev-neuron">​Neuron</​span></​html>​ \\
 +<​html><​span class="​dev-tag dev-axon">​Axon</​span></​html>​ \\
 +<​html><​span class="​dev-tag dev-extens">​Extension</​span></​html>​
 +;;#
 +</​WRAP>​
 +</​WRAP>​
 +
 +<WRAP center round box>
 +<​html><​span class="​kbBlue-H4alt">​Prerequisites</​span></​html>​
 +  * UniPi controller running Mervis OS
 +  * Basic project with attached controller a program in FBD mode
 +  * [[https://​www.unipi.technology/​power-supplies-c15|24 V⎓ power supply]]
 +  * Knowledge of how the [[en:​automation:​02-glossary:​analog-inputs-hidden|analog inputs]] work on UniPi units
 +
 +In this tutorial, we will use [[https://​www.unipi.technology/​cs/​neuron-c2|Unipi Neuron]].
 +</​WRAP>​
 +
 +===== Introduction =====
 +The different analog inputs have different modes of operation, see [[en:​automation:​02-glossary:​analog-inputs-hidden|Analog inputs]]. Change between modes in Mervis is done by configuring the Unipi module, therefor the **changes in modes cannot be done in the program** and the program has to be stopped during the configuration.
 +
 +<WRAP center round info 80%>
 + The default mode of each input is "​Voltage"​.
 +</​WRAP>​
 +
 +===== Changing between modes =====
 +The changes are done on the prototype of the PLC or Extension. Double click on the prototype in the **Left panel**. The list of all available inputs and outputs will show up in the **Main Window**. Search for "​AI_"​ and you will be presented with the list of all Analog input.
 +
 +{{ :​en:​sw:​01-mervis:​analog-inputs-01-search-for-ai.png?​direct |}}
 +
 +To change the mode, select appropriate variable from the list, head over to the **Properties panel** and select the desired mode in the "​Analog Type" property.
 +
 +{{ :​en:​sw:​01-mervis:​analog-inputs-02-set-type.png?​direct |}}
 +
 +We just changed the configuration of the PLC modules, which is not applicable by simply uploading the solution. To save the configuration,​ follow the [[en:​sw:​01-mervis:​unipi-configure-module-hidden|UniPi - Configure Module]] tutorial.
 +
 +===== Reading the input values =====
 +Reading the input values for all modes is the same. Once you set the correct mode, you can just simple read a real value from the variable. The variable is called AI_X.Y depending on the Group (number X) and the position in the group (number Y). To include this variable into the program, you need to **[[en:​sw:​01-mervis:​autogen-hidden|Set Autogen]]**. After that, you will see the variable in **Variable Browser** and you will be able to read it in the **Debugging** mode.
 +
 +<WRAP center round info 80%>
 +When reading the value of AO_X.Y in Voltage mode, the value is in volts (value 1.234 = 1.234 V⎓). When reading the value in Current mode, the value is in miliampers (value 3.145 = 3.145 mA). When reading the value in Resistance mode, tha value is in ohms (value 1012 = 1012 Ω)
 +</​WRAP>​