Analog outputs
Special functions
Stored data | Default configuration |
---|---|
Output mode | voltage output |
Output value | 0V |
Master Watchdog
This function runs on the section's (extension module's) microprocessor and continuously monitor the commands from the application running on the unit. If no commands are detected within a configured time (MWD Timeout), the module's processor automatically reboots and reverts to the default configuration described above. This function ensures a safe configuration is set in case of emergency situations (unit failure, communication error or software issues) to prevent damage to controlled devices or any hazards to personnel.
Technical parameters
Output terminals | AOV |
Common conductor | AGND |
Galvanic isolation | Yes |
Output functions | 0–10 V⎓ voltage source |
Resolution | 12 bits |
Conversion time | 300 μs |
Protection type | Integrated overvoltage protection |
Output voltage range | 0-10 V⎓ |
Output accuracy | ±0.5 % |