Technical parameters

Extension

The following article contains storage, installation and working conditions on Unipi Extension modules.

Terminal marking Meaning
+24V Power terminal - positive pole
GND Power terminal - negative pole
DI Digital input
DIGND Digital input common terminal – negative pole
RO Relay output
COM Common relay terminal
AI Analog input
AIR Analog input for resistance measurement
AIS Current source for resistance measurement
AOV Analog voltage output
AGND Analog input/output common terminal - negative pole
RS485-A / RS485-B RS-485 communication line terminals
Operating conditions Temperature 0 … +55 °C,
relative humidity 10 … 95 %,
without aggressive substances, condensing vapour and fog
Storing conditions Temperature -25 … +70 °C,
relative humidity 10 … 95 %,
without aggressive substances, condensing vapour and fog
Altitude up to 2000 m
EMC immunity zone B (IEC 61000-6-2 compliant)
Protection class I
Overvoltage category II
Pollution degree 2
Ingress Protection (IEC 529) IP 20
Operation position Any
Installation On 35mm DIN rail (EN 60715, 35mm) into distribution cabinet; holder and screws (M3x5, DIN 965, PH 1) included
Connection Pluggable terminal blocks
Wire gauge Max. 2.5 mm2
Terminal spacing 5.08 mm
Terminal tightening torque Max. 0.4 Nm

Power supply

Rated voltage - SELV 24 V⎓ (±5%)
Power consumption Typ. 3 W
Max. 12 W
Reverse polarity protection Yes

Dimensions and weight

Dimensions 72 × 90 × 56 mm (DIN holder 3 mm)
Weight depending on the model - from 140 g to 300 g

Unipi Extension xS:

Input type SINK
Input terminal DI
Common ground DIGND
Log. 0 < 3 V DC
Log. 1 > 7 V DC
Maximum voltage 35 V DC
Non-defined state 3-7 V DC
Input resistance for TRUE 6 200 Ω
Voltage drop on DI diode 1.2 V
Minimum pulse length 20 μs
0–>1 / 1–>0 delay Typ. 20 μs / 60 μs
Maximum CNT counter input frequency 10 kHz
LED indication Yes
Galvanic isolation Yes (Basic, between DI groups)
Insulation voltage (pulse) 1500 V

(i)

Please note: The data below represent a selection of the most important parameters and serve only as a quick reference.

Detailed information can be found in the product datasheet provided by the relay manufacturer: FTR-F3AA024E-HA

Output type Electromechanic non-shielded relay
Output terminal RO
Common terminal COM
Contact type Normally open (SPST-NO)
Used relay type FTR-F3AA024E-HA
Maximum switching voltage 250 V AC
30 V DC
Maximum switching current 5 A
Maximum common terminal current 10 A
Short-term current overload 5 A
Mechanical lifespan 5 000 000
Electrical lifespan Up to 100 000 (according to the connected load)
Operate/release time 10 ms
Designed for load character AC-15, DC-13 (resistive)
Load handling External (RC, varistor, diode, thermistor)
Short circuit protection No
Overvoltage protection No
LED indication Yes
Galvanic isolation Yes (Basic)
Insulation voltage (pulse) 2500 V between RO and RO
4000 V between RO and all other circuits

/!\

Warning:
Only extra-low voltage (ELV) can be connected to the relay output RO 1 of Unipi Extension xS5* modules (xS51, xs52, etc.)! The parameters specified above must also be respected.

Input terminals AI, AIS
Common conductor AGND
Galvanic isolation Yes
Input functions 0–10 V⎓ voltage measurement,
0–20 mA current measurement,
0–1960 Ω or 0–100 kΩ resistance measurement
Resolution 24 bits (resistance measurement),
16 bits (voltage and current measurement)
Conversion time 400 ms (resistance measurement),
60 μs (voltage and current measurement)
Protection type Integrated overvoltage protection
Maximum input voltage 15 V⎓
Measurement accuracy ±0.2 %
Input resistance (voltage measurement) 44 kΩ
Input resistance (current measurement) 100 Ω
Input terminals AI / AIS
Common ground AGND / AIR
Overvoltage protection Integrated transil
Maximum voltage 15 V⎓
Maximum current 40 mA
Connection SINK (measurement relative to the ground)
Galvanic isolation (pulse) 1500 V between AI and all other circuits

(!)

Attention:
Measurements outside the specified range may reduce the accuracy of the measurement and/or reduce the input impedance.

In case of strong interference to the cable (EN 6100-6-4), the measurement accuracy can be reduced to 1 % of the measured value. The use of additional EMC filters and shielded cabling is recommended (connect shield to the ground point of the device).

Voltage 0-10 V

Available on device xS53, xS54
Measuring range 0.1–10 V
Accuracy ±0.2 % (of range)
Input resistance 12 kΩ ±20 %
Resolution 24 bits
Conversion time 200 ms

Voltage 0-2 V

Available on device xS53, xS54
Measuring range 0.1–2 V
Accuracy ±1 % (of range)
Input resistance 1 MΩ ±50 %
Resolution 24 bits
Conversion time 200 ms

Current 4-20 mA

Available on device xS53, xS54
Measuring range 1–20 mA
Accuracy ±0.2 % (of range)
Input resistance 100 Ω ±1 %
Resolution 24 bitů
Conversion time 200 ms

Resistance 2 kΩ

Available on device xS52, xS54
Measuring range 75–2000 Ω
Connection Two-wire
Measuring current < 0.3 mA (average)
Resolution 24 bits
Accuracy ±0.3 % (of value) / 0.5 Ω
Conversion time 200 ms
Compatible sensors Pt100/Pt1000 (tol. ±0.75 ˚C),
Ni100/Ni1000/2k reostat,
etc..

(i)

Please note:
The compensation of the lead resistance and the conversion to temperature according to the selected sensor is up to the user application.

Resistance 20 kΩ

Available on device xS52, xS54
Measuring range 1–20 kΩ
Connection Two-wire
Measuring current < 0.03 mA (average)
Resolution 24 bits
Accuracy ±1 % (of value) / 10 Ω
Conversion time 200 ms
Compatible sensors Reostat
Output terminals AOV
Common conductor AGND
Galvanic isolation Yes
Output functions 0–10 V⎓ voltage source
Resolution 12 bits
Conversion time 300 μs
Protection type Integrated overvoltage protection
Output voltage range 0-10 V⎓
Output accuracy ±0.5 %
Terminals RS485-A, RS485-B
Baudrates 2400 bps
4800 bps
9600 bps
19200 bps
38400 bps
57600 bps
115200 bps
Pull-up/pull-down resistors No
Terminating resistor Builtin attachable, 120 Ω
(RS485-END)
Galvanic isolation (pulse) 1500 V between RS-485 and all other circuits