Connecting Mervis IDE to Weintek HMI panel using the BACnet/IP protocol
HMI panels are useful devices that can make control of various automation projects (boiler control, smart home control, industrial production control etc.) much easier. If you then need to connect HMI panel to the Mervis IDE, you can do so using the BACnet protocol over LAN.
In this tutorial, we will show you how to set up a BACnet server, how to connect a client to this server and how to generate a variable list (EDE file).
About BACnet
- The protocol uses Client-Server model
- The client access data via server-side objects (A/D values, trend logs etc.)
Things you will need:
- Unipi PLC with Mervis OS v2.2.0 or newer
- 24V DC power supply for the Unipi PLC
- Local network connectivity (switch or router)
- 2× RJ45 network cable
- EasyBuilder PRO program (also contains a simulator)
- Weintek HMI display with Ethernet, or Weintek HMI simulator
- + 24 V DC power supply for the HMI display
- + 1× network patch (RJ45) cable for the HMI display
Useful additional info:
- Creating a new project in the Mervis IDE
- Yet Another BACnet Explorer (YABE) – a software to access BACnet network
- A Modbus guide for connecting the HMI to a Unipi PLC with Mervis OS
- Mervis OS update guide and latest Mervis IDE installer
Connection example:
1 Basic Mervis IDE settings
Create a new Mervis IDE project or open an already existing project. Follow the following guide:
Create a server channel by right-clicking on PLC and choosing
Add Server Channel.
Name the new channel
BACnet_server.
Select the newly created
BACnet_server
and set the protocol type to
BACnetServer.
Right-click on the
BACnet_server
server channel
and choose
Add Server Device.
Name the newly created device
BACnet_UDP.
Select the device and set the same parameters in
Properties
in as following:
- Device instance: 1 (1 - 4 194 302, unique within the network)
- Management Password: set your password
- IP Address: 0.0.0.0
- Device Port: 47808
2 Variables, mapping and linking
Next step is to create
BACnet objects
and link them to a local or global variable. This step is very important to allow the client to read or write to variables. There are 2 ways to do this:
Note: It is possible to link unused variables to BACnet objects. However, Mervis IDE will warn you that server variables could not be loaded, and that image could not be created. The reason is the variable is not used for compilation and the BACnet object thus does not have any variable to link to.
The picture depicts the above-described situation with unused variables.
                                           
2.1 Variables, mapping and linking
Click on the
BACnet_UDP
device and then right-click into the blank space. A pop-up menu will appear – choose
Add Variable.
A drop-down variable list will appear. Choose a variable you wish to read or write to via the Weintek HMI.
A BACnet server variable will become available. Click on
Build Solution
in order to generate BACnet object parameters (identifier, type, etc…) – until now, these were displayed only as
n/a.
The result should look like this. You now have your first
BACnet object
including its ID.
2.2 The alternative way: directly through the Variable Browser
In the
Variable Browser
look up the variable you want to make available for the BACnet server to read from/write to, and check the
PLC:BACnet visible
checkbox.
A drop-down menu will appear. In
PLC: BACnet Device,
choose the BACnet device you want to make the variable available for. In our case the tab will be pre-filled with
BACnet_UDP.
Check the following picture for reference:
If you now click on the
BACnet_UDP
device, the Mervis IDE should display all previously selected objects.
Now click on
Build Solution.
By doing so the BACnet object parameters will update and new parameters will be generated.
The result for adding two objects should look like this:
You can now deploy the solution by clicking on
Deploy Solution.
All changes you made will be uploaded into the PLC.
3 EDE file export (optional step)
EDE files
are useful if your BACnet client is unable to automatically detect objects on the BACnet server, or if you want to set up client device without access to BACnet server.
Right-click on
BACnet_server
and choose
Export EDE file.
You will need these files to import the variable settings into the client, so the display will know which variables it should read or write to. Any exported EDE files can be found in the
/“Project_Name“/export
subfolder.
Examples of exported EDE files:
4 EasyBuilder PRO settings, simulator/HMI download
Download, install and run the
EasyBuilder PRO
software tool.
Create a new project for your HMI display model. If you don’t have the HMI display, you can choose the MT6071iP/MT8071iP as on the picture below.
Upon creating the new project, a
System Parameter Settings
will appear. Click on
New device/server.
A new window with several additional settings will appear. Enter the following parameters:
- Name: BACnet/IP (Device)
- Location: local
- Device type: BACnet/IP
- I/F: Ethernet
Now click on the
Settings...
button.
In this tab you can set up the IP address either manually, or you can click on
Who Is…
and the server will be found and set up automatically. The standard BACnet port is 47808 – if you selected a different port in Mervis IDE, you need to change the BACnet port here as well.
Caution: Make sure that no other application is listening on the same port on your PC. If it would listen on the same port, the
Who Is…
option would be unable to find any servers and the simulation would not communicate with the BACnet server.
Confirm all changes and click on the newly created
BACnet/IP
tab. Then click on
Tag Manager…
Now click on
Get Tag Info…
to automatically download objects from the BACnet server (Mervis). If the variable info cannot be downloaded, please check if the port is not already used.
Select BACnet objects you wish to use – in our case select everything. Confirm all changes and close the settings window:
You should now see an empty HMI window which is used to insert various graphics elements.
Let’s test it by creating a single
Toggle Switch
and a single
Bit LampThe Tag tab serves for object mapping..
In the list you can see objects available on the Unipi PLC. Please choose a DO for Toggle Switch. Then look up the
hw_$Axon S105_DO_1_01_w$
object and select
PresentValue.
For
Bit lamp
choose one of the
DI
variables.
Look up the
hw_$Axon S105_DO_1_01_w$
object and select
PresentValue.
The result should look like this.
Note the displayed info about which BACnet object is linked to the graphics element.
Now click on
Compile
Upon compilation you can now either load the HMI project into the HMI display, or you can start the simulator.
- If you have HMI display, click on Download (PC -> HMI)
- If you want to use the simulator, click on Online Simulation
Note: The
Offline simulation
option cannot be used, as the simulation would not be able to connect to the PLC.
5 Result
Now check the HMI or the simulation. You can see that the state of DI1 is being displayed on the Bit lamp object which glows blue when the DI is active. Also, by clicking on the Toggle switch, you can switch the value of DO1.
Check the PLC’s LED indicators. If you followed all steps and the communication is running OK, states of DI1 and DO1 on the PLC presented by the LEDs will correspond to the states on the HMI/simulation.