Using the IEC 60870-5-104 Protocol

Patron Gate

Mervis RT includes the functionality of an IEC 60870-5-104 server to provide data access to third parties. For example, it is used to regulate output power of power stations connected to the ČEZ distribuce network.

For the IEC 60870-5-104 protocol to function, Mervis RT must be activated with an extended license that includes this protocol. To get it, contact the sales department of Unipi.

Running IEC 60870-5-104 server is certified only on Patron and Gate units, it can not be used on other Unipi controllers.

As with other protocols, using the IEC 60870-5-104 protocol requires defining a server channel of the appropriate type at the PLC level.

Let's add a Server Channel:

Adding a server channel

We set its protocol to IEC 60870-5-104 and set desired protocol parameters.

Setting protocol and IEC parameters

Now, we add a server device, select it by clicking on it and we can set server parameters and add a datapoint.

Adding a server device and datapoints

One or more devices can be defined on the channel, differing in the set Common Address (ASDU) and TCP port.

  • Enable - True/False
  • Link Protocol - TCP only

IEC 60870-5-104 Protocol Parameters

  • Maximum Number of Unacknowledged APDU (K-value)
  • Maximum Number of Unacknowledged APDU (W-value)
  • Timeout of Acknowledgement (t1) - time interval
  • Timeout of Acknowledgement via S-frame (t2) - time interval
  • Timeout of Test Frame (t3) - time interval
  • Check Maximum Delay of Control Commands - True/False
  • Maximum Delay of Control Commands - time interval
  • Remap Types for Interrogation - True/False
    • During initial interrogation, data types with time stamps will be replaced with data types without time stamps.

Device properties include parameters for connecting clients to the server:

  • Enable - True/False

TCP Parameters

  • IP Address
    • The address of the network interface on which the server should listen. Currently, only the value 0.0.0.0 for all interfaces is supported.
  • Port - The TCP port on which the server listens. Default value 2404

IEC 60870-5-104 Protocol Parameters

  • Common Address (ASDU)

IEC 60870-5-104 Data Point Parameters

  • Identification Object Address
  • Identification Object Type
  • Mapped Variable
M_SP_NA_1 [1] Single point information
M_SP_TA_1 [2] Single point information with time tag
M_DP_NA_1 [3] Double point information
M_DP_TA_1 [4] Double point information with time tag
M_ST_NA_1 [5] Step position information
M_ST_TA_1 [6] Step position information with time tag
M_BO_NA_1 [7] Bitstring of 32 bits
M_BO_TA_1 [8] Bitstring of 32 bits with time tag
M_ME_NA_1 [9] Measured normalized value
M_ME_TA_1 [10] Measured normalized value with time tag
M_ME_NB_1 [11] Measured scaled value
M_ME_TB_1 [12] Measured scaled value with time tag
M_ME_NC_1 [13] Measured short floating point value
M_ME_TC_1 [14] Measured short floating point value with time tag
M_ME_ND_1 [21] Measured normalized value without quality descriptor
M_SP_TB_1 [30] Single point information with CP56Time2a time tag
M_DP_TB_1 [31] Double point information with CP56Time2a time tag
M_ST_TB_1 [32] Step position information with CP56Time2a time tag
M_BO_TB_1 [33] Bitstring of 32 bits with CP56Time2a time tag
M_ME_TD_1 [34] Measured normalized value with CP56Time2a time tag
M_ME_TE_1 [35] Measured scaled value with CP56Time2a time tag
M_ME_TF_1 [36] Measured short floating point value with CP56Time2a time tag
C_SC_NA_1 [45] Single command
C_DC_NA_1 [46] Double command
C_RC_NA_1 [47] Regulating step command
C_SE_NA_1 [48] Set-point command, normalised value
C_SE_NB_1 [49] Set-point command, scaled value
C_SE_NC_1 [50] Set-point command, short floating point value
C_BO_NA_1 [51] Bitstring command, 32 bits
C_SC_TA_1 [58] Single command with CP56Time2a time tag
C_DC_TA_1 [59] Double command with CP56Time2a time tag
C_RC_TA_1 [60] Regulating step command with CP56Time2a time tag
C_SE_TA_1 [61] Set-point command, normalised value with CP56Time2a time tag
C_SE_TB_1 [62] Set-point command, scaled value with CP56Time2a time tag
C_SE_TC_1 [63] Set-point command, short floating point value with CP56Time2a time tag
C_BO_TA_1 [64] Bitstring command, 32 bits with CP56Time2a time tag