Alarms

For an overview of large projects or a larger number of projects, there is an alarm overview tab. There is also a history of alarms available.

(i)

Looking for more details about the individual alarm states?

The alarm overview is opened by clicking on the button with the alarm icon [🕭] in the upper right corner ([5] in the screenshot below). But first you need to set the alarms.

[1] Tree Overview

The overview on the left shows a list of project names. Next to the project name is a number that represents the total number of alarms for this project.

[2] Current Alarms

The overview shows all current data points in alarm. For each data point, there is information about the alarm status.


Active Alarm

Clicking invokes a dialog box with information about the alarm value, the time the alarm occurred, and the current time. In the window, you can confirm the alarm, display it in the project, or just close the dialog box.


Acknowledged Alarm

The dialog box no longer allows confirming the alarm. Additionally, it contains information about the time the alarm was confirmed.

[3] Filtering data points in the Alarm overview

You can filter using the buttons on the panel (described below) and the Filter search field.

(i)

Note:
To filter across all projects, you must first click the show all alarms button

Show active alarms
Show acknowledged alarms
Show alarms from all projects
Alarm history range
Reload data
Show/hide history panel
Acknowledge all selected
Reset all selected
Download history
(i) Show information about highlighted/selected data point
Priority update of the highlighted/selected data point

[4] Alarm history

History shows the time of alarm creation/cancellation, who (which user) acknowledged the alarm, and the current state of the alarm. The history can be sorted by the time of alarm creation/cancellation and three Filters: path / data point / user

Each point that has active alarm behavior can, depending on the settings, take on different alarm states and gradually transition between these states, as shown in the following image.

  • Texts in circles correspond to the alarm state
  • Arrows between them represent the following transitions between states
    • Red arrow - alarm activation
    • Blue solid arrow - alarm cancellation
    • Blue dashed arrow - alarm cancellation with enabled automatic reset
    • Ack - alarm acknowledgment
    • Reset - alarm reset
    • If an action is triggered that is not shown in the diagram, it is ignored (e.g., reset request in the Normal state)