Analog inputs
Extension
Special functions
Default configuration
This function is used to save the current configuration of the section (extension module) into its memory. In the case of power cycle of the device or reboot of the section (extension module), the stored configuration is loaded and applied. This functionality is also known as “copy
running-config to startup-config”.
| Stored data | Default configuration |
|---|---|
| Measurement mode | voltage measurement |
Master Watchdog
This function runs on the section's (extension module's) microprocessor and continuously monitor the commands from the application running on the unit. If no commands are detected within a configured time (MWD Timeout), the section's (extension module's) processor automatically reboots and reverts to the default configuration described above. This function ensures a safe configuration is set in case of emergency situations (unit failure, communication error or software issues) to prevent damage to controlled devices or any hazards to personnel.
Technical parameters
| Input terminals | AI, AIS |
| Common conductor | AGND |
| Galvanic isolation | Yes |
| Input functions | 0–10 V⎓ voltage measurement, 0–20 mA current measurement, 0–1960 Ω or 0–100 kΩ resistance measurement |
| Resolution | 24 bits (resistance measurement), 16 bits (voltage and current measurement) |
| Conversion time | 400 ms (resistance measurement), 60 μs (voltage and current measurement) |
| Protection type | Integrated overvoltage protection |
| Maximum input voltage | 15 V⎓ |
| Measurement accuracy | ±0.2 % |
| Input resistance (voltage measurement) | 44 kΩ |
| Input resistance (current measurement) | 100 Ω |