Technical parameters

Edge

The following article contains technical details of communication interfaces on Edge units, as well as the unit's storage, installation and working conditions.

Terminal marking Meaning
+24V Power terminal - positive pole
GND Power terminal - negative pole
DI Digital input
COM Digital input common terminal – negative pole
DO Digital output
AI Analog input
AG Analog input ground terminal - negative pole
SA / SB RS-485 communication line terminals
ETH Ethernet port
μHDMI micro HDMI port
USB USB A 2.0 port
INIT USB-C port (for service only)
WiFi Wireless antenna interface
μSIM micro sim slot
LTE MAIN Main LTE antenna interface
CAT4 DIV / GNSS Cat 4 diversity LTE or GNSS antenna interface
SVC Service button
Control type by purpose Operating control
Control type by design Independently mounted control
Operating conditions Temperature -20 ... +60 °C, relative humidity 10 ... 95 %, without aggressive substances, condensing vapor and fog
Storing conditions Temperature -40 ... +85 °C, relative humidity 10 ... 95 %, without aggressive substances, condensing vapor and fog
Ingress Protection (IEC 529) IP 20
Installation On 35 mm DIN rail (EN 60715, 35 mm) into distribution cabinet; holder and screws included
Operation position Horizontal inside vertical enclosure
Altitude up to 2000 m
EMC immunity zone B (IEC 61000-6-2 compliant)
Protection class III
Overvoltage category II
Pollution degree 2
Automatic action control type 1
Software function class A
Control function class A

Temperature dependence of CPU & GPU core frequency:

(!)

Attention:
Core temperature is usually higher from ambient temperature by about 20 °C. The temperature difference can vary depending on actual load of CPU and GPU cores, ventilation of enclosure, used DIN rail holder and DIN rain length.

Power supply

Reverse polarity protection Yes
Rated voltage - SELV (recommended) 24 V⎓
Absolute maximum ratings 10.2 V⎓* to 32.2 V⎓
Power supply wire gauge see Connectors
Variant LTE Cat 1 / Cat 4 Without LTE
Typical input current (at rated voltage 24 V⎓) 0.25 A* 0.18 A*
Maximum input current (at rated voltage 24 V⎓) 1 A* 0.7 A*

(i)

* Valid only for basic variants without any expansion boards.

(!)

Attention:
In case of high power demand (when full LTE transmit power required and 100% CPU load) in high ambient temperature near the limits use 24 V⎓ power supply. Using lower power supply voltage (e.g. 12 V⎓) may cause the internal protection to trip.

Connectors

Connector purpose For power supply Other terminals
Connector model xinya XY2500F-B DEGSON 15EDGKNHC-3.5
Min. wire gauge 0.75 mm2 (AWG18) 0.2 mm2 (AWG24)
Max. Wire gauge 2.5 mm2 (AWG14) 1.5 mm2 (AWG16)
Terminal pitch 5.08 mm 3.5 mm
Terminal tightening torque Max. 0.4 Nm -
Connection Pluggable terminal blocks Pluggable terminal blocks

Dimension and weight

Dimensions (W x H x D) 108 × 90 × 56 mm (6 DIN modules)
Weight Depending on specific model - approx. 200-290 g
DIN holder variants Default Alternative
Name AL TSH-35
Thickness between device and DIN rail 3.5 mm 7 mm
Holder weight 61 g 14 g
Holder material Aluminium Plastic
Holder screws (included) 3x M3x5, flat head 2x M3x7 mm, button head

Unipi Edge front view (sizes in mm):


Unipi Edge side view (sizes in mm):
left - alternative (TSH-35) DIN holder
right - default (AL) DIN holder

Input terminals DIx
Common ground COM
Input type SINK
Voltage for FALSE -3 … 5 V ⎓
Voltage for TRUE 9 … 35 V ⎓
Indeterminate state 5 … 9 V ⎓
Maximum voltage 35 V ⎓
Input resistance for TRUE 6 200 Ω
Voltage drop on DI diode 1.2 V
Minimum pulse length 20 μs
FALSE –> TRUE delay 20 μs
TRUE –> FALSE delay 60 μs
Maximum CNT counter input frequency 10 kHz
Input functions Counter (including memory), Direct Switch
Galvanic isolation Yes, see illustration below (Functional, cannot exceed SELV)

Internal isolation of DIs

Output terminals DOx
Output connections A, B
Output type Solid state MOSFET relay
Output load type Resistive load (specific values are listed below)
Maximum switching voltage 48 V ⎓
Switching current continuous (up to 25°C) 500 mA
Rate of current reduction (above 25°C) 5 mA for each 1 °C
Switching current pulse 1.5 A
Highest short-circuit current 6 A
Total rated load 48 V⎓, 500 mA
Inductive load protection No, external snubber needed
Maximum switching speed 500 Hz / 8 bit
Functions of output PWM
PWM Maximum frequency (recommended) 200 Hz
PWM Maximum resolution 16 bits
Galvanic isolation Yes, see illustration below (Functional, cannot exceed SELV)

Internal isolation of DOs

(!)

Attention:
Each analog input have corresponding ground terminal located below. Connecting to any other ground terminal may result in higher measuring inaccuracy, worse EMC and bypasses integrated protection.

Input terminals AIx
Ground conductors AGx
Type of input SINK (measurement relative to the ground)
Input functions 0–10 V⎓ voltage meas.
0–2.5 V⎓ voltage meas.
4–20 mA current meas.
90–2000 Ω resistance meas.
Protection type Integrated overvoltage
Maximum input voltage 15 V⎓
Maximum input current 25 mA
Galvanic isolation Yes, see illustrations below (Functional, cannot exceed SELV)

(!)

Attention:
Measurements outside the specified range may reduce the accuracy of the measurement and/or reduce the input impedance.

In case of strong interference to the cable (EN 6100-6-4), the measurement accuracy can be reduced to 1 % of the measured value. The use of additional EMC filters and shielded cabling is recommended (connect shield to the ground point of the device).

Voltage 0-10 V

Available on inputs AI1, AI2, AI3
Measuring range 0.1–10V
Accuracy ±0.2 % (of range)
Input resistance approx. 13.9 kΩ
Resolution 24 bit
Conversion time 100 ms

Internal isolation of AI for 10 V measuring mode

Voltage 0-2.5 V

Available on inputs AI2, AI3
Measuring range 0.1–2.5V
Accuracy ±0.2 % (of range)
Input resistance approx. 13.9 kΩ
Resolution 24 bit
Conversion time 100 ms

Internal isolation of AI for 2.5 V measuring mode

Current 4-20 mA

Available on inputs AI2, AI3
Measuring range 4–20 mA
Accuracy ±0.2 % (of range)
Input resistence approx. 100 Ω
Resolution 24 bit
Conversion time 100 ms

Internal isolation of AI for 4-20 mA measuring mode

Resistance 90-2000 Ω

Available on inputs AI4, AI5
Connection Two-wire
Measuring range 90–2000 Ω
Measuring current < 0.3 mA (average)
Resolution 24 bit
Accuracy ±0.1 % (in operational temperature range)
Conversion time 100 ms
Compatible sensors Pt100/Pt1000 (tol. ±0.3 ˚C + 0.03 °C/K over 50 °C ambient),
Ni100/Ni1000/2k reostat,
etc..

(!)

Note:
The compensation of the lead resistance and the conversion to temperature according to the selected sensor is up to the user application.

Internal isolation of AI for 2 kΩ measuring mode

32 channels were periodically cycled in temperature range. Min. and Max. deviation from actual value across all cycles of ambient temperature

RS-485 Terminals SxA, SxB
Negative connection (D-) A
Positive connection (D+) B
Galvanic isolation Yes, see illustration below (Functional, cannot exceed SELV)
ESD protection ±15 kV
Communication speeds 50 baud
150 baud
300 baud
600 baud
1 200 baud
2 400 baud
4 800 baud
9 600 baud
19 200 baud
38 400 baud
57 600 baud
115 200 baud
230 400 baud
460 800 baud
500 000 baud
576 000 baud
921 600 baud
1 000 000 baud
1 152 000 baud
1 500 000 baud
2 000 000 baud
2 500 000 baud
3 000 000 baud
Input impedance approx. 1.2 kΩ
Input voltage hysteresis 30 mV
Output characteristic ±2.3 V
Terminating resistor Built-in attachable 120 Ω
(S-END)
RS-485 pull-up / pull-down resistors 560 Ω / 560 Ω

Internal isolation of RS-485

Ethernet ports ETH 1x 1 Gbps
1x 100 Mbps (optional)
USB ports 1x USB-C (for service only)
2x USB 2.0 (optional)
Graphical interface 1x μHDMI (optional)
Resolution of graphical output up to 4Kp60

Wireless LAN (optional)

Wi-Fi standard 2.4 GHz, 5.0 GHz IEEE 802.11b/g/n/ac
Bluetooth Bluetooth 5.0 with BLE
WLAN Diversity 1×1 SISO
Antenna connector 1x RP-SMA female

LTE (optional)

Variant Cat 1 Cat 4
Modem manufacturer Quectel Quectel
Modem type EC200U-EUAB
EC200U-EUAP
EC200A-EUHA
Category and transmission speed Cat 1 (10/5 Mbps) Cat 4 (150/50 Mbps)
FDD Bands B1/3/4/7/8/20/28 B1/3/5/7/8/20/28
TDD Bands B38/40/41 B38/40/41
GSM GSM900/DSC1800 GSM900/DSC1800
GPRS class 12 12
EDGE class - 12
GSM900 Radio frequency power (max.) 33 dBm ±2 dB 33 dBm ±2 dB
DSC1800 Radio frequency power (max.) 30 dBm ±2 dB 30 dBm ±2 dB
LTE-FDD Radio frequency power (max.) 23 dBm ±2 dB 23 dBm ±2 dB
LTE-TDD Radio frequency power (max.) 23 dBm ±2 dB 23 dBm ±2 dB
Sim card type microSIM microSIM
Antenna connectors 1x SMA female (MAIN)
+1x additional SMA female for GNSS variants
2x SMA female (MAIN, DIV)
GNSS (EC200U-EUAP only) GPS, GLONASS, BeiDou, Galileo, QZSS -

(!)

Note:
For information about peripherals and how to access them in the OS see Peripherals section.

TPM

TPM version Trusted Platform Module 2.0
Manufacturer Infineon
Model OPTIGA SLB 9672
Bus SPI (33 MHz)

Retain

Memory size 128 kB (default)
Memory type NVRAM
Bus SPI (30 MHz)
Model MB85RS1MT
Lifespan 1013 times / byte

RTC

Battery CR2032 lithium battery
Bus I2C
Model MCP79410
Lifetime approx. 10 years

Block diagram of Unipi Edge E410 (full variant)

This website uses cookies. By using the website, you agree with storing cookies on your computer. Also you acknowledge that you have read and understand our Privacy Policy. If you do not agree leave the website.More information about cookies